CALL US :+386 41 612 309         Slovensko   English  
All prices include VAT !

Poseidon2 model 3266 Tset[3266]

Poseidon2 model 3266 Tset[3266]

Your Price : 728,34 €
Quantity :

Poseidon2 model 3266 is independent device which can send Email when a contact is switched on or when temperature or humidity gets out of set range. Except Email, Poseidon model 3266 can send SNMP Trap. Values and configuration are accessible from WWW graphic interface, sensor's values over several network protocols (SNMP, XML, Modbus/TCP and others).

 

Poseidon model 3266 can notice operator of crisis situation in various method (switched on/switched off contact, temperature or humidity out of set range).

When a Alarm occurs, the device sends you Email and notice Your NMS (Network Management Software) over SNMP.

Configuration and current values over graphic WWW interface.

  • 4 Dry contact inputs for contacts connecting
  • You can connect up to 8 temperature or humidity sensors.
  • To connect sensors (over maximal distance of 10 meters) you can use standard phone adaptors, cables and connectors RJ11 or RJ12.
  • Contact switch on -> sending email or SNMP Trap to several recipients.

Application

 

  • Security: supervising of sensors in IT rooms.

  • SCADA systems: connecting of external inputs

  • Monitoring of back-up power source: UPS and Diesel engines

  • Monitoring of operating conditions: (temperature and humidity) ICT technologies (fire, security and phone systems)

  • Logging of processes: storages, cold-storage rooms, freezers and fridges (food industry and pharmacy)

  • IT – monitoring:  server rooms, 19“ racks (ICT)

  • Camera systems: external sensors connecting(door contact, PIR)

  • Large buildings: heating and air-condition optimalization

  • Systems interconnecting:  fire (EPS), security (EZS), access system

  • Air-condition monitoring: temperature and evaporated water leaking

  • Supervising systems: Information points, ATM, terminals 
     

What Poseidon2 3266 measures

Sensors are connected over 1-Wire (RJ12), total wiring length must not exceed 10 meters. Each sensor monitors whether the value is in set range (including inputs for connecting contacts). It warns about set range exceeding (Alarm status) via Email or sending SNMP trap.
 

Compatible probes

  • Temperature - Temp-1Wire
    Temperature probes, different lengths of connecting cables according to ordering number:
    600 005 = 3 meters long, 600 242 = 1 meters long, 600 056 = 10 meters long)

  • Humidity - Humid-1Wire
    Humidity probe, long:
    600 279 = 3 meters long, 600 278 = 1 meters long)

  • 4 inputs for Dry Contact

    • Door contact

    • Flood detector

    • Gas leak detector

    • Smoke detector

    • Motion detector


Basic features

  • It can be connected to every monitoring system of building, industry, IT and networks.

    • Support and plug-in modules for many NMS application (LoriotPro, Nagios, SNMPc, HP OpenView, IBM Tivoli, MRTG and others).

    • Works with most SCADA systems (OPC server and I/O server over Modbus/TCP)

  • Graphic WWW interface for configuration and values monitoring.

    • Configuration and current values over simple graphic interface (web browser)

  • Open communication protocols (WEB, Email, SNMP, XML, Modbus/TCP)

    • Notification of Alarm status- Email, SNMP Trap, SMS (via SW).

  • One  Poseidon 3266 unit monitors up to 7 external probes (4 contacts, 3 sensors over a bus), every sensor has unique ID.

    • We supply temperature and humidity sensors in different design and cable lengths (1 / 3 / 10 meters).

  • Security increased with password, IP address range, HW protection against configuration changes.

  • No SW necessary.

    • Set of supporting programs and utilities (PN Eye, Pos-Excel, PD Trigger and others)

    • We supply programs for food industry (CapTemp), IT monitoring (nmsDashboard) and others

    • SDK (Software Development Kit) development library available + examples (VB, Delphi, C, C#etc.)

  • For OEM partners who order 50 pieces or more option to change device name, HTML design contact list and other.

  • FirmWare update over WWW interface

      Technical specification

Poseidon 3266: 4 Dry contact inputs, 1-Wire bus, Ethernet 10 Base-T, DIP switches

  • Port 1: Ethernet RJ 45 - 10BASE-T / 10 Mbit/s

  • Port 2: SENSORS - 1-Wire bus (RJ12)

  • Port 3: 4 Dry Contact input for contact connecting

  • Power supply : 12V SS

  • Device setting:

    • Locally - RS-232 Setup

    • UDP Config

    • Over WEB - graphic Flash setup interface

    • Over SNMP  


 

Port 1 - Ethernet port

 

+ Interface

RJ45 (10BASE-T) – 10 Mbit or 10/100 Mbit network compatible

+ Supported protocols

IP: ARP, TCP/IP (HTTP, Modbus over TCP), UDP/IP (SNMP)

+ SNMP compatibility

Ver:1.00 compatible, some parts of the ver 2.0 implemented

 

Port 2 - 1-Wire sensor bus

 

+ Connector

RJ12 (6 pins - 4 pins used only)

+ Sensors / distance

model 3265 - max. 5 sensors, up to 10 m total
model 3262 - max. 2 sensors, up to 10 m total

 

Port 3 - Dry contact inputs

 

+ 4 Contact inputs

Connect it with a contact directly (dry contact).

+ Isolation

Galvanic isolated up to 50V DC

+ Sensor type

NO or NC contact switch

+ Max distance

Up to 30 m

 

LED Status indicators

+ POWER

Green - power OK

+ LINK & Activity

Yellow - Ethernet connectivity

 

DIP SWITCH configuration

+ DIP1   - RS--232 Setup mode

Not used

+ DIP2   - Security

ON   = Security mode - remote configuration disabled
OFF = Non-Security mode - remote configuration enabled

 

Physical parameters

 

+ Voltage requirements

9 - 15V / 250 mA DC
coaxial power connector (barrel), GND on the shield

+ Dimensions

35 x 101.6 x 76.2 [mm] (H x W x D )

+ Weight

150 g

 

Functional parameters

 

Device SETUP configuration possibilities

- UDP Config - IP address assign via UDP with using PN Eye
- TCP Setup - Terminal configuration and sensors management
- WWW Setup - HTTP Flash application
- SNMP (just for some parameters)


 

  • Accessories for the IT bus (1-Wire / RJ12)

    • Poseidon T-Box  [600 040]
      Hub for up to 5 probes over 1-Wire bus (5x RJ12), connecting cable 0,1 meter long.

       

    • Poseidon T-Box2  [600 280]
      Hub for up to 2 probes over 1-Wire bus (2x RJ12), connecting cable 3 meter long.

       

    • Temp-1Wire (temperature probe)

    • Humid-1Wire (humidity probe)

       

  • Accessories for Dry Contact Inputs

    • Door contact  [600 119]
      Magnetic sensor for door opening detection - small, easy to use..

    • PowerEgg
      Detection of external AC voltage (110 to 230V), configurable AC output(110 to 230V)

    • Flood detector (water leak detection with autonomous sirene)

    • Gas leak detector (Gas leak detection with autonomous sirene)

    • Smoke detector (Smoke and fire detection with autonomous sirene)

    • Motion detector


Manufacturers