The Poseidon2 model 3268 is a small web server that can send Email, when a contact is switched or when temperature and humidity gets out of preset range. You can also control two relay outputs from web interface and turn off e.g. a server. The model 3268 notifies of an alarm via Email, SNMP Trap or via switching output relay. Internal memory of 250.000 points.
Poseidon2 model 3268 can notice operator of crisis situation in various method (switched on/switched off contact, temperature or humidity out of set range).
When a Alarm occurs, the device sends you Email and notice Your NMS (Network Management Software) over SNMP.
Configuration and current values over graphic WWW interface.
- 2 relay outputs to control external devices
- 4 inputs to connect contact
- You can connect up to 8 temperature or humidity sensors.
- IT bus to connect sensors (over up to 10m), standard phone switch, cables and connectors can be used
- Typical use:
- Switch contact to send email or SNMP Trap to several recipients.
- Turn on external cooling fan and notify an operator after temperature gets out of preset range.
|
Application
-
IT – control: switch on/off or restart connected devices
-
Security: supervising of sensors in IT rooms.
-
SCADA systems: connecting of external inputs
-
Monitoring of back-up power source: UPS and Diesel engines
-
Monitoring of operating conditions: (temperature and humidity) ICT technologies (fire, security and phone systems)
-
Logging of processes: storages, cold-storage rooms, freezers and fridges (food industry and pharmacy)
-
IT – monitoring: server rooms, 19“ racks (ICT)
-
Camera systems: external sensors connecting(door contact, PIR)
-
Large buildings: heating and air-condition optimalization
-
Systems interconnecting: fire (EPS), security (EZS), access system
-
Air-condition monitoring: temperature and evaporated water leaking
-
Supervising systems: Information points, ATM, terminals
What Poseidon 3268 measures
Sensors are connected over 1-Wire (RJ12), total wiring length must not exceed 10 meters. Each sensor monitors whether the value is in set range (including inputs for connecting contacts). It warns about set range exceeding (Alarm status) via Email or sending SNMP trap.
Compatible probes
-
Temperature - Temp-1Wire
Temperature probes, different lengths of connecting cables according to ordering number:
600 005 = 3 meters long, 600 242 = 1 meters long, 600 056 = 10 meters long)
-
Humidity - Humid-1Wire
Humidity probe, long:
600 279 = 3 meters long, 600 278 = 1 meters long)
-
4 inputs for Dry Contact
-
Door contact
-
Flood detector
-
Gas leak detector
-
Smoke detector
-
Motion detector
Basis features
-
It can be connected to every monitoring system of building, industry, IT and networks.
-
Support and plug-in modules for many NMS application (LoriotPro, Nagios, SNMPc, HP OpenView, IBM Tivoli, MRTG and others).
-
Works with most SCADA systems (OPC server and I/O server over Modbus/TCP)
-
Graphic WWW interface for configuration and values monitoring.
-
Open communication protocols (WEB, Email, SNMP, XML, Modbus/TCP)
-
One Poseidon 3268 unit monitors up to 8 external probes (4 contacts, 4 sensors over a bus), every sensor has unique ID.
-
Security increased with password, IP address range, HW protection against configuration changes.
-
No SW necessary.
-
Set of supporting programs and utilities (Pos-Excel, PD Trigger and others)
-
We supply programs for food industry (CapTemp), IT monitoring (nmsDashboard) and others
-
SDK (Software Development Kit) development library available + examples (VB, Delphi, C, C#etc.)
-
For OEM partners who order 50 pieces or more option to change device name, HTML design contact list and other.
-
FirmWare update over WWW interface
HW interface
Overview of all sensors in our assortment: Sensors and accessories.
-
Digital Outputs (Relay switch)
2 switching contacts of internal relay (output contact can be used as a NO (Normally Open) or NC(Normally Close))
-
Digital Input (Dry Contact input)
4x input to connect contact (door for example) or output from relay (pins labled as NO or NC)
-
IT Bus - RJ12 (1-Wire)
A bus for use in IT, designed to connect temperature and humidity sensors over up to 10m
Technical specification
-
Port 1: Ethernet RJ 45 - 10BASE-T / 10 Mbit/s
-
Port 2: SENSORS - 1-Wire bus (RJ12)
-
Port 3: 4 Dry Contact input for contact connecting
-
Port 4: 2 switching outputs of internal relay
-
Power supply : 12V SS
-
Device setting:
Port 1 - Ethernet port
|
|
+ Interface
|
RJ45 (10BASE-T) – 10 Mbit or 10/100 Mbit network compatible
|
+ Supported protocols
|
IP: ARP, TCP/IP (HTTP, Modbus over TCP), UDP/IP (SNMP)
|
+ SNMP compatibility
|
Ver:1.00 compatible, some parts of the ver 2.0 implemented
|
|
Port 2 - 1-Wire sensor bus
|
|
+ Connector
|
RJ12 (6 pins - 4 pins used only)
|
+ Sensors / distance
|
model 3265 - max. 5 sensors, up to 10 m total
model 3262 - max. 2 sensors, up to 10 m total
|
|
Port 3 - Dry contact inputs
|
|
+ 4 Contact inputs
|
Connect it with a contact directly (dry contact).
|
+ Isolation
|
Galvanic isolated up to 50V DC
|
+ Sensor type
|
NO or NC contact switch
|
+ Max distance
|
Up to 30 m
|
|
Port 4 - Relay switch outputs
|
|
+ 2 Digital outputs
|
Control via network (Web, XML, SNMP) or signal local alarm
|
+ Isolation
|
Relay switch up to 50V DC, max DC current 24V/1A, 50V/0.5A
|
+ Switch type
|
3 pins, can be used as NO or NC contact switch
|
|
LED Status indicators
|
+ POWER
|
Green - power OK
|
+ LINK & Activity
|
Yellow - Ethernet connectivity
|
|
DIP SWITCH configuration
|
+ DIP1 - RS--232 Setup mode
|
Not used
|
+ DIP2 - Security
|
ON = Security mode - remote configuration disabled
OFF = Non-Security mode - remote configuration enabled
|
|
Physical parameters
|
|
+ Voltage requirements
|
9 - 15V / 250 mA DC
coaxial power connector (barrel), GND on the shield
|
+ Dimensions
|
35 x 101.6 x 76.2 [mm] (H x W x D )
|
+ Weight
|
150 g
|
|
Functional parameters
|
|
Device SETUP configuration possibilities
|
- UDP Config - IP address assign via UDP with using PN Eye
- TCP Setup - Terminal configuration and sensors management
- WWW Setup - HTTP Flash application
- SNMP (just for some parameters)
|
-
Accessories for the IT bus (1-Wire / RJ12)
-
Poseidon T-Box [600 040]
Hub for up to 5 probes over 1-Wire bus (5x RJ12), connecting cable 0,1 meter long.
-
Poseidon T-Box2 [600 280]
Hub for up to 2 probes over 1-Wire bus (2x RJ12), connecting cable 3 meter long.
-
Temp-1Wire (temperature probe)
-
Humid-1Wire (humidity probe)
-
Accessories for Inputs (Dry Contact)
-
Door contact [600 119]
Magnetic sensor for door opening detection - small, easy to use..
-
PowerEgg
Detection of external AC voltage (110 to 230V), configurable AC output(110 to 230V)
-
Flood detector (water leak detection with autonomous sirene)
-
Gas leak detector (Gas leak detection with autonomous sirene)
-
Smoke detector (Smoke and fire detection with autonomous sirene)
-
Motion detector
-
Accessories for Output (internal relays)